Cold Shirnkable Straingth Termiantions suitable for 3 Core XLPE/EPR/PVC Insulated Cables upto 36 KV
GCXO/i- 1236
Descriptions:
GCXO/I - 1236 - Series termination kits are cold shrinkable type, designed for 3 core extruded dielectric, shielded, armoured & unarmoured XLPE/EPR/PVC insulated cables upto 36 KV rated voltage (12KV, 15-24KV & 36KV usage). It is based on specially formulated, trackresistant, silicone rubber insulators with stress relief. These insulators are pre-stretched around a coiled plastic core. When the termination is slipped over a properly prepared cable and the core is pulled out, the termination immediately shrinks to fit the cable's dimensions. The result is a tight, durable, void free, constant-pressure seal for a variety of cable types and sizes. Our kits provide a dielectric constant of approximately 25, distributing the electric field well beyond the shield cut off. These are designed, manufactured and tested according to requirements of the local & internationally accepted standards.
Salient Features:
- Simple installation - no special tools required
- No torches or heat required
- Safe installation - replaces conventional & simple method
- Accommodates a wide range of cable sizes
- Built in Stress control mechanism
- Improved tough rubber formulation withstand rough backfilling
- Resistant to acids, alkalis, ozone, UV light, and fungus
- Minimized Chances of Jointer error
- Maintains constants radial pressure.
- No torches or heat required.
- Built in Stress Control mechanism
- Maintains Constants radial pressur.
Specifications:
Test Sequence | 12 kV | 24kV | 36 kV |
---|---|---|---|
A.C. Voltage Withstand, 5 Min | 28.5 kV, no Flashover | 57.1 kv, no Flashover | 85.5 kV, no Flashover |
D.C. Voltage Withstand, 15 Min | 25.4 kV, no Flashover | 50.8 kv, no Flashover | 76 kV, no Flashover |
Impulse Withstand Voltage | 75 kV, no Flashover | 125 kv, no Flashover | 170 kV, no Flashover |
Partial Discharge | 12 kV < 10Pc Max | 24 kV < 10Pc Max. | 36kV < 10pc Max. |
Order Reference:
12 kv Systems | 15-24 Kv Systems | 36 kV Systems | |
Cable Size (Sq. mm) | Kit Code | Kit Code | Kit Code |
---|---|---|---|
16-50 | GCXO-11 | GCXO-21 | GCXO-31 |
70-95 | GCXO-12 | GCXO-22 | GCXO-32 |
120-185 | GCXO-13 | GCXO-23 | GCXO-33 |
240-300 | GCXO-14 | GCXO-24 | GCXO-34 |
400 | GCXO-15 | GCXO-25 | GCXO-35 |